Exhaust systems are used to remove air that contains contaminants, including odours. Some HVAC designs also rely on the operation of exhaust fans to create negative pressure that draws outdoor air into the building through windows and gaps in the building envelope.
19. Confirm that exhaust fans are operating
Use chemical smoke to confirm that air is flowing into the exhaust grille(s).
20. Verify that local exhaust fans remove enough air to eliminate
odours and chemical fumes
If the fan is intended to exhaust the entire room, stand outside the room with the door slightly open and use chemical smoke to confirm that air is being drawn into the room from locations both high and low in the door opening.
If the fan is running, but air isn't flowing toward the exhaust intake (or not enough air is moving to do the job), check for the following possibilities:
21. If the exhaust fan is located close to the contaminant source, rather than on the roof, and exhaust air is ducted through the building under positive pressure
Confirm that the exhaust ductwork is sealed and in good condition. Make any repairs permanent and take any other measures that help ensure there will be adequate outdoor air in the future.
This section provides basic guidance and options for determining air movement and measuring outdoor air supply. It is divided into three sections:
Both flow hoods and pitot tubes can be used to measure airflow. Flow hoods are designed to measure flow at grilles and diffusers. Pitot tubes and anemometers are designed to measure air velocity in ducts, which is then used to calculate airflow. While flow hoods are more expensive to purchase, they are quicker and easier to use. Flow hoods can be used to measure airflow in ducts by adding the airflows from all vents connected to a given duct.
Often, the amount of duct leakage is significant. By comparing the total airflow at the fan to the sum of all vents connected to the fan, an estimate of the duct leakage can be determined. If the variation is large or the sum of the vents is greater than the fan capacity, further investigation should be undertaken.
22. Using Chemical Smoke to Determine Air Flow Direction
Chemical smoke can help with evaluation of HVAC systems, tracking air and pollutant movement, and identifying pressure differentials. Chemical smoke moves from areas of higher pressure to areas of lower pressure if there is an opening between them (e.g., door, utility penetration).
Because chemical smoke is the same temperature as the surrounding air, it is extremely sensitive to air currents. Investigators can learn about airflow patterns by observing the direction and speed of smoke movement. Smoke released near outdoor air intakes will indicate whether air is being drawn into the intake. Puffs of smoke released at the shell of the building (by doors, windows, or gaps) will indicate whether the HVAC systems are maintaining interior spaces under positive or negative pressure relative to the outdoors.
Chemical smoke is available with various dispensing mechanisms, including smoke "bottles," "guns," "pencils," or "tubes". The dispensers allow smoke to be released in controlled quantities and directed at specific locations. It is often more informative to release several small puffs of smoke as you move along an air pathway rather than a large amount in a single puff.
Caution: Read the equipment manufacturer's information. Chemical smoke devices may use titanium tetrachloride to produce smoke. Although the small amounts of chemicals produced during testing are normally not hazardous, you should avoid inhaling smoke from these devices. The concentrated fumes from smoke devices can be very corrosive.
Puffs of smoke released near HVAC vents give a general idea of airflow. (Is it in or out? Vigorous? Sluggish? No flow?) This is helpful in evaluating the supply and return system and determining whether ventilation air actually reaches the breathing zone. For a variable air volume system, be sure to take into account how the system is designed to modulate. The system could be on during the test, but off for most of the rest of the day. "Short-circuiting" occurs when air moves directly from supply diffusers to return grilles, instead of mixing with room air in the breathing zone. If a substantial amount of air short-circuits, school occupants may not receive adequate supplies of outdoor air and pollutant emissions may not be diluted sufficiently.
Chemical smoke can also be used to assess the performance of fume hoods and exhaust fans. If the smoke released at a certain point is not captured, neither will any other contaminant.
23. Measuring Outdoor Air Supply Quantity
This section describes methods for determining the amount of outdoor air supplied by a single ventilation unit, using either a flowhood or air velocity measurement device. These are general instructions for measuring airflow. You should also follow the instructions provided by the manufacturer of your measuring equipment.
Step 1. Determine Airflow Quantity
Using a flowhood
Flowhoods measure airflow in cubic feet per minute (CFM) or litres per second (Lps) at a diffuser or grille. To measure airflow, hold the flowhood up to the diffuser and read the airflow value. Follow the instructions supplied with the flowhood regarding its use, care, and calibration.
Using Velocity Measurements
For information on measuring air velocity using a pitot tube or anemometer, and calculating outdoor air supply, see the instructions supplied with the equipment.
Airflow in ductwork can be estimated by measuring air velocity at various positions in the duct cross-sections. The airflow instrument should have instructions for conducting this procedure (airflow traverse).
Measure the air velocity in the duct and calculate the airflow by multiplying the area-averaged velocity times the cross sectional area of the duct.
Systems with No Mechanically Supplied Outdoor Air
If the ventilation system does not use mechanically supplied outdoor air, the amount of outdoor air infiltrating the area can be estimated. Estimate air infiltration by measuring the quantity of air exhausted by exhaust fans serving the area.
Using a small floor plan, such as a fire escape map, mark the areas served by each exhaust fan.
Measure airflow at grilles or exhaust outlets using a flowhood. Determine the airflow in ductwork by conducting an airflow traverse.
Add the airflows from all exhaust fans serving the area to determine the total air exhaust.
24. Estimating Outdoor Air Using Carbon Dioxide Measurements
Carbon dioxide (CO2) is a normal part of the atmosphere. Exhaled breath from building occupants and other sources increase indoor CO2 levels above the levels found in outdoor air. CO2 should be measured with a direct-reading meter. Use the meter according to manufacturer's instructions. Indoor CO2 concentrations can, under some test conditions, be used to assess outdoor air ventilation. A comparison of peak CO2 readings between rooms and between air handler zones may help to identify and diagnose various building ventilation deficiencies.
Estimating the quantity of outdoor air supply for mechanical systems
Take CO2 readings, with minimal delays between readings, at supply outlets or air handlers to estimate the percentage of outdoor air in the supply airstream.
The percentage or quantity of outdoor air is calculated using CO2 measurements as shown below:
Outdoor air (%) = (CR-CS) divided by (CR-CO) x 100
Where: CS = CO2 parts per million (ppm) in the supply air (if measured in a room), or in the mixed air (if measured at an air handler)
CR = ppm of CO2 in the return air
CO = ppm of CO2 in the outdoor air (Typical range is 300-450 ppm.)
All these concentrations must be measured, not assumed.
To convert the outdoor air percentage to a volume of outdoor air in litres per second, use the following calculation:
Outdoor air (Lps) = Outdoor air (percent) / 100 x total airflow (Lps)
The number used for total airflow may be the air quantity supplied to a room or zone, the capacity of an air handler, or the total airflow of the HVAC system. However, the actual amount of airflow in an air handler is often different from the quantity stated in design documents. Only the measured airflow is accurate.
Record the number of school occupants, time of day, position of windows and doors, and weather for each period of CO2 testing.
Note locations where CO2 concentrations are 1,000 ppm or higher. Short-term conditions where CO2 levels exceed 1000 ppm may indicate temporary ventilation problems caused by increased occupancy or ventilation system changes. Chronic conditions where CO2 levels exceed 1000 ppm (for several hours on each of several days) may indicate the need for increased ventilation, or a modification in the space occupancy or use.
Note that there may still be under-ventilation problems in rooms with peak CO2 concentrations below 1,000 ppm. CO2 is produced by human respiration (breathing), and concentrations can change rapidly as people move in and out of a room. Four to six hours of continuous occupancy are often required for CO2 to approach peak levels.
All activities on this checklist have been completed and no help is required.
OR
A list of problems and/or assistance required is attached.
Air Handling Log - DRAFT
Instructions:
Name
Room or Area
School
Date Completed
Signature
Activity
Activity Number
Notes and Comments
Indoor Air Quality Tools for Schools Action Kit for Canadian Schools
We anticipate revising the Tools for Schools Action Kit in the future. To help us ensure that the Kit meets the needs of those who are using it, please send us your comments about how easy or difficult you found the Kit to use. Suggestions for how to make the Kit more useful are especially welcome. If a reply is requested, please provide your name, address and phone number along with the completed sheet and mail it to:
Comments or Suggestions:
Your role at the school (e.g., custodial staff, teacher, etc.):
Checklist (s) used:
Optional for correspondence purposes:
Name:
Address:
Telephone:
Fax:
E-mail: